![](http://pdfasset.owneriq.net/7/e7/7e7331a3-1407-4eac-b438-ad6cdcee7231/7e7331a3-1407-4eac-b438-ad6cdcee7231-bg8c.png)
4 - 20 4 - 20
MELSEC-Q
4 SETTING AND PROCEDURE BEFORE OPERATION
REMARKS
Check the test condition and error details with the following link special register
areas.
• Baton pass status (host) (SW0047) → 1FH: Offline test
• Cause of baton pass interruption (SW0048) → 2H: Offline test
• Offline test execution item/faulty station (requesting side) (SW00AC) → 9H:
Hardware test
• Offline test result (requesting side) (SW00AD) → 0: Normal, 1 and later: Error
code