![](http://pdfasset.owneriq.net/7/e7/7e7331a3-1407-4eac-b438-ad6cdcee7231/7e7331a3-1407-4eac-b438-ad6cdcee7231-bg10d.png)
7 - 33 7 - 33
MELSEC-Q
7 APPLICATION FUNCTIONS
(2) Station No. settings
For the master module mounted on the station (multiplexed remote master
station) to which the system A connector of tracking cable is connected, set the
station No.0.
If the station No. other than 0 is set, the programmable controller CPU will detect
the LINK PARA. ERROR (error code 3101).
For the master module mounted on the station (multiplexed remote sub-master
station) to which system B connector of tracking cable is connected, set the
station No. in the range of 1 to 64. If the station No. 0 is set, the programmable
controller CPU will detect the LINK PARA. ERROR (error code 3101).