Mitsubishi Electronics QJ71LP21 Universal Remote User Manual


 
App - 17 App - 17
MELSEC-Q
APPENDICES
Table 3 Link special register (SW) list (Continued)
No. Name Description
Availability
Control
station
Normal
station
Remote
master
station
Remote I/O
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
SW0033
(51)
ZNWR instruction
processing result
Indicates the processing result of the ZNWR instruction.
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
Send/receive instruction
(2) processing result
Indicates the processing results of the SEND/RECV/READ/
WRITE/REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/
REMTO instructions (when physical channel 2 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW0035
(53)
Send/receive instruction
(3) processing result
Indicates the processing results of the SEND/RECV/READ/
WRITE/REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/
REMTO instructions (when physical channel 3 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW0037
(55)
Send/receive instruction
(4) processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 4 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW0039
(57)
Send/receive instruction
(5) processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 5 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW003B
(59)
Send/receive instruction
(6) processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 6 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW003D
(61)
Send/receive instruction
(7) processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 7 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW003F
(63)
Send/receive instruction
(8) processing result
Indicates the processing results of the SEND/RECV/READ/WRITE/
REQ/RECVS/RRUN/RSTOP/RTMRD/RTMWR/REMFR/REMTO
instructions (when physical channel 8 is used).
0 : Normal completion
Other than 0 : Abnormal completion (refer to the error codes
in Section 8.3)
SW0040
(64)
Network No.
Stores the network number of the host.
Range: 1 to 239
SW0041
(65)
Group No.
Stores the group number of the host.
0 : No group designation
1 to 32 : Group No.
SW0042
(66)
Station No.
Stores the station No. of host station.
1 to 64 : Station No.
7DH : Remote master station
SW0043
(67)
Mode status
Stores the mode status of the host.
0 : Online
2 : Offline
3 or more : Applicable test