Mitsumi electronic AJ65BT- 64DAV/DAI TV Converter Box User Manual


 
3. SPECIFICATIONS MELSEC-A
3-9
Table 3.3 Analog output status combination list
HOLD/CLEAR setting CLEAR HOLD
Analog output enable
signal
Enable (on) Prohibit (off) Enable (on)/Prohibit (off)
Setting
combination
Execution
status
Analog output
enable/disable flag
Enable (0) Prohibit (1) Enable (0) Prohibit (1) Enable (0) Prohibit (1)
Analog output status when the programmable
controller CPU is in the RUN status
Output of the
analog value
after D/A
conversion
from the digital
value specified
by the
programmable
controller CPU
0V/0mA
Offset
value
0V/0mA
Output of the
analog value
after D/A
conversion
from the
digital value
specified by
the
programmable
controller CPU
0V/0mA
Analog output status when the programmable
controller CPU is in the STOP status
Offset value 0V/0mA
Offset
value
0V/0mA
Analog value
before the
programmable
controller CPU
stop is
retained.
0V/0mA
Analog output status when the programmable
controller CPU is in the error status
Offset value 0V/0mA
Offset
value
0V/0mA
Analog value
before the
CPU error is
retained.
0V/0mA
Analog output status when an error has
occurred in the AJ65BT-64DAV/DAI
Output of the
maximum or
minimum
analog value
0V/0mA
Offset
value
0V/0mA
Output of the
maximum or
minimum
analog value
0V/0mA
Analog output status when a WDT error (*)
has occurred in the AJ65BT-64DAV/DAI
0V/0mA
Analog output status when the L.RUN LED is
turned off (when link communications are
shut off)
Offset value 0V/0mA
Offset
value
0V/0mA
Analog value
before the
LINK ERR is
retained.
0V/0mA
Analog output status after reset
Output of the
analog value
after D/A
conversion
from the digital
value specified
by the
programmable
controller CPU
0V/0mA
Offset
value
0V/0mA
Output of the
analog value
after D/A
conversion
from the
digital value
specified by
the
programmable
controller CPU
0V/0mA
(*) WDT error ...........indicates the abnormal operation time by the programmable controller. The
elapsed time for one scan by the program is monitored, and a WDT error results
when it does not finish within the scheduled time.