Mitsumi electronic AJ65BT- 64DAV/DAI TV Converter Box User Manual


 
5. PROGRAMMING MELSEC-A
5-14
*Checking of AJ65BT-64DAV status
*Changing of initial settings
*Initial settings
*Processing at initial settings
*Setting of digital values
*Analog output enable/disable specification
Reads data link status
AJ65BT-64DAV data
link normal
AJ65BT-64DAV data
link abnormal
Offset/gain value selection
(RY04)
Analog output enable/
disable setting (RWw4)
Turns on initial data
processing completion
flag (RY18)
CH.1 digital value setting
(RWw0): 50
CH.2 digital value setting
(RWw1): 100
CH.3 digital value setting
(RWw2): 200
CH.4 digital value setting
(RWw3): 300
Turns on initial data setting
request flag (RY19)
Offset/gain value selection
(RY04)
Analog output enable/
disable setting (RWw4)
Turns on initial data setting
request flag (RY19)
Turns off initial data
processing completion
flag (RY18)
Turns off initial data setting
request flag (RY19)
Turns on CH.1 analog output
enable/disable flag (RY00)
Turns on CH.2 analog output
enable/disable flag (RY01)
Turns on CH.3 analog output
enable/disable flag (RY02)
Turns on CH.4 analog output
enable/disable flag (RY03)
*1: The program enclosed by the dotted line is necessary only when the initial settings are changed.
Initial setting change
Digital
value
setting
Analog
output
enable
*1