4. SETUP AND PREPARATION BEFORE OPERATION MELSEC-A
4-5
Point
(1) Set the offset and gain values in the actual usage state.
(2) The offset and gain values are stored in the AJ65BT-64DAV/DAI, and are not erased even
the power supply is shut off.
(3) Perform the offset/gain setting when the programmable controller CPU is stopped. When in
the test mode, D/A conversion is stopped for all channels, so use the remote READY signals
as an interlock.
(4) Perform the offset/gain setting in the range from DC -10 to +10V or from 4 to +20mA. When
the setting exceeds this range, the maximum resolution or total precision may not be in the
range indicated in the performance specification.
4.4 Station Number Setting
By the AJ65BT-64DAV/DAI station number setting, the addresses to store the control I/O signal data
and read/write data are determined.
For details, refer to the user's manual of the master module used.
4.5 Facing Direction of the Module Installation