Sterling 882.000254.00 Home Theater Server User Manual


 
7/50D Plus or 7/50D Controller Chapter 4: Operation 60
Enabling and Disabling Stations and Pumps
When a station or pump is disabled, the controller makes no attempt to use it and ignores any
alarms that occur for it. Disabling a station or pump at the controller’s screen is similar to
bypassing a station with its bypass switch. Enabling a station or pump makes it available for
use. (For a station to be available for the system, it must be enabled at the controller’s screen
and its bypass switch must be in the “0” position.)
To enable or disable a station (or pump):
1. Go to the Station Summary (or Pump Summary) screen, if needed.
To reach this screen from any other screen, touch Stations (or Pumps) on the
right-hand side of the screen.
Each disabled station (or pump) has an icon with a status of “offline” (black with a
gray outline). All other statuses are enabled statuses.
2. Touch the icon for the station (or pump) briefly.
The station (or pump) switches to the new state, as indicated by the color of its icon.
Note: If the Station n Operator (or Pump n Setup) screen appears when you
touch the icon, then you have kept your finger on the screen too long.
Touch Stations (or Pumps) to return to the Summary screen and
try again. If you find it difficult to touch the icon briefly enough, ask
the setup personnel at your facility to lengthen the touch switch delay.