Transferring Stations to a Standby Pump
If a pump fails, you can transfer all of the controller’s station assignments for that pump to a
standby pump. To do this, you must disable (take offline) both the source pump and the
standby pump, and the standby pump must have no stations already assigned to it.
The transfer operation at the controller’s touch screen merely changes the pump assignment
for every station on the failed pump. It does not transfer any pumps settings for auto
shutdown delay, alarms, or blow-back to the standby pump. Mechanical connections must be
changed manually.
To transfer stations from a pump to a standby pump:
1. At any screen, touch Pumps.
The Pump Summary screen appears.
2. Both the source pump and the standby pump must be offline. If either pump is any
other state, disable it by touching its icon briefly.
The icon becomes black with a gray outline.
3. Move the vacuum hose from the failed pump to the standby pump, and carry out any
other mechanical procedures needed to use the standby pump.
4. At the Pump Summary screen, touch and hold the icon for any pump until the Pump
n Setup screen appears.
5. At the Pump n Setup screen, touch Transfer Stations To Standby Pump.
The Transfer to Standby Pump screen appears: