G7 ASD Operation Manual 117
Drooping Reference
Program Feedback Parameters Drooping Control Drooping
Reference
This parameter sets the method to be used in determining the output torque
while operating in the Drooping Control mode.
Settings:
Total Torque Calculated by the Detection Current.
Torque without Acc/Dec Torque Calculated by Detection Current.
Total Torque Calculated by the Command Current.
Torque without Acc/Dec Torque Calculated by the Command Current.
Direct Access Number — F327
Parameter Type — Selection List
Factory Default — Total torque
calculated by the detection current
Changeable During Run — Ye s
Light-load High-speed Operation Selection
Program Special Control Parameters Crane/Hoist Settings
Express Speed Settings Light-Load High-Speed Operation
This parameter enables the Light-Load High-Speed function by selecting an
operating mode. The Light-Load High-Speed function accelerates the output
frequency of the ASD from the programmed speed to the setting established in
F341.
This parameter may be disabled.
If either of the other selections are made and configured, and after the
criteria of
F331 F333 are met, the Light-Load High-Speed function is
enabled and this parameter determines the operating mode of the Light-Load
High-Speed function.
Settings:
Disabled
Reserved
Automatic Enable - Automatic Speed (F341)
Automatic Enable - Preset Speed (Preset ID
Bin
is OR’ed w/1000
Bin
)
Discrete Enable - Automatic Speed (F341) (see item 60 of Table 8 on pg. 76)
Discrete Enable - Preset Speed (Preset ID
Bin
is OR’ed w/1000
Bin
) (see item
60 of
Table 8 on pg. 76)
Direct Access Number — F330
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Minimum — 30.0
Maximum — Upper Limit (F012)
Units — Hz
Light-Load High-Speed Operation Switching Lower-Limit
Frequency
Program Special Control Parameters Crane/Hoist Settings
Express Speed Settings Light-Load High-Speed Operation
Switching Lower-Limit Frequency
This parameter sets an output frequency threshold that, once surpassed, allows
the Light-load High-speed function to be used.
The Light-Load High-Speed function may be used if the frequency threshold
(
F331) and the following conditions are met:
1) Light-Load High-Speed Operation Enable is configured at F330.
2) The output torque is less than the setting established in F335 when reaching
the frequency setting here.
Direct Access Number — F331
Parameter Type — Numerical
Factory Default — 40.00
Changeable During Run — Ye s
Minimum — 30.0
Maximum — Upper Limit (F012)
Units — Hz
F327 F331