G7 ASD Operation Manual 195
Cable/Terminal Specifications
Note: Input and Output power wires require shielding for CE compliance.
Note: (*) Indicates that the item is one of a set of two parallel cables.
Installation should conform to the 2002 National Electrical Code Article 110 (NEC) (Requirements for
Electrical Installations), all regulations of the Occupational Safety and Health Administration, and any
other applicable national, regional, or industry codes and standards.
Note: The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the ASD. Application-specific applicables, wire insulation type,
conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the ASD.
Note: Cable/Terminal specifications are based on the rated current of the ASD and Do Not
include the 10% Service Factor.
For further installation information see the section titled Installation and Connections on pg. 17.
Table 18. 230-volt G7 ASD Cable/Terminal Specifications.
Model
VT130G7U
MCP
Rating
(Amps)
Typical Wire/Cable Size (AWG or kcmil) Lug Size Range
Input/Output Power
AM, FM, and II
Terminals
Control Terminals
Wire-Size/Lug-Capacity for
Input/Output Power
Recommended Maximum
2010B 15 14 10
20
(3-core shield)
18
(2-core shield)
24 to 8
2015B 15 14 10
2025B 15 14 10
2035B 20 14 10
2055B 30 12 10
2080B 50 10 10
2110B 50 8 4
18 to 42160B 75 6 4
2220B 100 4 4
2270B 125 3 2 16 to 1
2330B 150 2 2
10 to 1/0
2400B 175 1/0 2/0
2500B 200 2/0 2/0 12 to 4/0
2600B 250 *1/0 *4/0
*(6 to 250)
2750B 300 *2/0 *4/0
210KB 400 *4/0 *500
*(1/0 to 500)212KB 500 *300 *500
215KB 600 *400 *500