![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/b/0d/b0dbd200-eacc-4ea1-9b49-6a9ab5783b83/b0dbd200-eacc-4ea1-9b49-6a9ab5783b83-bg4a.png)
68 G7 ASD Operation Manual
Speed Reach Frequency
Program ⇒ Terminal Selection Parameters ⇒ Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter
F102, will provide a signal at an
output terminal that can close an appropriately configured output contact (see
Table 9 on pg. 81 for the available output assignments).
Direct Access Number — F101
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Speed Reach Frequency Tolerance
Program ⇒ Terminal Selection Parameters ⇒ Reach Settings
This parameter sets the bandwidth of the Speed Reach Frequency (F101)
setting.
Direct Access Number — F102
Parameter Type — Numerical
Factory Default — 2.5
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F101 F102