Specifications
Power requirements 301C
17-27 Vac, 50/60 Hz, 8.64 VA
18-36 Vdc, 350mA @ 24 Vdc (8.4 VA)
Operating temperature range
-20°C to 50°C (-4°F to 122°F)
Operating humidity range
0 to 95% RH (non-condensing)
Operating altitude
Up to 3000 m (9843 ft)
Network capacity
Up to 96 transmitters, 32 per channel
Channels 1, 2 = Modbus and Vulbus
Channel 3 = Modbus only
Communication
Up to 609m (2,000 ft) per channel
User interface
Graphic 122 x 32 dot matrix backlit display
User friendly keypad
Visual indicators
Power Green LED
Alarm A, B, C Red LED
Fault Amber LED
Tx Amber LED
Rx Green LED
Outputs
4 DPDT relays
Output rating
5A, 30Vdc or 250 Vac (resistive load)
Audible alarm
65dBA at 1 m (3 ft)
Time delays
Programmable Before and After delays
Battery
3 volt lithium battery
Enclosure
ABS-polycarbonate - indoor use
Dimensions (HxWxD)
28 x 20.3 x 7cm (7.99” x 11.02” x 2.76”)
Certifications
ANSI/UL 61010-1
CAN/CSA C22.2 No. 61010-1
ETL 116662
103