Honeywell 301C Home Theater Server User Manual


 
Honeywell 301C User Manual
Base Objects
76
Data Type
Required
1
Storage
Type
2
BACnet
Writeable?
Value
object_identifier
R
C N
46344 (or 0xB508) for Relay #1 up to
46347 (or 0xB50B) for Relay #4
object_type enumerated
R C
N
binary_output (4)
event_state
enumerated
R
C N
normal (0)
object_name
character string R
N N
"device_object_name
.relX", where
device_object_name is programmed on the
LUI and defaults to "VA301C:1" and X is
relay number (1 to 4). Thus the default
object_name for Relay #4 will be
"VA301C:1.rel4"
out_of_service boolean R C
N
FALSE
polarity
enumerated
R C
N
always Normal (0)
present_value
enumerated R
R
Only
Rly1&2. Not
Rly 3or4.
True state of the relays. These take the
value of the highest-priority BACnet
command. If no BACnet command, this
takes the value of the associated event.
priority_array R
R N
last value written
reliability
enumerated
0 C N
no_fault_detected (0)
relinquish_default
R
C
N
not meaningful
active_text
character string
O C N
"ON"
inactive_text
character string O
C
N
"OFF"
status_flags
in_alarm
boolean R C
N
always "false" (0)
fault
boolean R
C N
always "false" (0)
overridden
boolean
R R N
always "false" (0)
out_of_service
boolean
R R N
always "false" (0)
object_identifier R C N 46360 (or 0xB518)
object_type enumerated R C
N
binary_output (4)
event_state
enumerated R C
N
normal (0)
object_name
character string R
N N
"device_object_name.buzz", where
device_object_name is programmed on the
LUI and defaults to "VA301C:1" . Thus the
default object_name will be
"VA301C:1.buzz"
out_of_service boolean R
C N
FALSE
polarity
enumerated
R C N
always Normal (0)
present_value
enumerated R
R Y
True state of the buzzer. This takes the
value of the highest-priority BACnet
command. If no BACnet command, this
takes the value of the associated event.
priority_array R R
N
last value written
reliability
enumerated 0
C N
no_fault_detected (0)
relinquish_default
R
C N
not meaningful
status_flags
in_alarm boolean R C
N
always "false" (0)
fault
boolean R C N
always "false" (0)
overridden
boolean R C N always "false" (0)
out_of_service
boolean R C N always "false" (0)
Notes
1 -- 'R' indicates that this property is required by ASHRAE Standard 135
'O' indicates that the property is optional in ASHRAE Standard 135
2 -- 'C' indicates the property is hard-coded as a constant
'N' indicates the property is stored in non-volatile memory
'R' indicate the property is computed constantly and stored in RAM.
buzz rel1 to rel4
Binary Outputs
Group Property