15 FUNCTIONS (FUNCTION VERSION B OR LATER)
15.9.3 Execution procedure for the temporary error invalid station specification function
The execution procedure for the temporary error invalid station specification function is
as follows:
Turn on the temporary error invalid station request. (SB0004)
Turn off the power supply of the temporary error invalid station,
and replace the module.
Turn on the temporary error invalid station canceling request. (SB0005)
Turn on the power supply of the temporary error invalid station.
Select whether or not to specify multiple stations as temporary
error invalid stations. (SW0003)
(00: multiple stations specification, 01 to 64)
POINT
(1) Even if a temporary error invalid station specification is executed to the station
where an error has already occurred, the error information will not be cleared.
This specification is valid only when executed to the error occurred after the
temporary error invalid station specification has been executed.
(2) "The temporary error invalid request" and "temporary error invalid canceling
request" given to the station specified as the error invalid station with
parameters become invalid.