Mitsubishi Electronics Q68ADV TV Converter Box User Manual


 
App. - 10 App. - 10
MELSEC-Q
APPENDIX
Appendix 2.3 OGSTOR
Restores the offset/gain values of the user range setting stored in the CPU to the A/D
converter module.
Usable devices
Internal device
(System, user)
MELSECNET/H
Direct J \
Constant
Set data
Bit Word
File
register
Bit Word
Special
function
module
U
\G
Index
register
Z
K, H S
Other
(S) ———
(D) ———
Command
G.OGSTOR
Command
GP.OGSTOR
Un (S) (D)
Un (S) (D)
[Instruction
symbol]
[Execution
condition]
G.OGSTOR
GP.OGSTOR
Set data
Device Description Setting range Data type
Un Start I/O number of the module 0 to FE
H
Binary 16 bits
(S)
1
Start number of the device in which control data is stored.
Within the range of the
specified device
Device name
(D)
Device that is turned ON 1 scan on completion of dedicated
instruction processing.
(D) + 1 also turns ON at an abnormal completion.
Within the range of the
specified device
Bit
1 When executing the G.OGLOAD instruction, specify the device designated in (S).
Do not change the data read with the G.OGLOAD instruction.
If it is changed, normal operation cannot be guaranteed.
Control data of Q64AD (1/2)
Device Item Set data Setting range Set by
(S) System area
——
(S) + 1 Completion status
Stores the status when the instruction
is complete.
0 : Normal completion
Other than 0: Abnormal completion
System
(S) + 2 Pass data classification setting
The value set to Pass data
classification setting (S)+2 using the
G.OGLOAD instruction is stored.
0: Voltage specified
1: Current specified
0
0 CH.4 CH.3 CH.2 CH.1
b15 b4b3b2b1b0
0000
H
to 000F
H
User
(S) + 3 System area
(S) + 4 CH1 Industrial shipment settings offset value System
(S) + 5 CH1 Industrial shipment settings gain value System
(S) + 6 CH2 Industrial shipment settings offset value System
(S) + 7 CH2 Industrial shipment settings gain value System
(S) + 8 CH3 Industrial shipment settings offset value System
(S) + 9 CH3 Industrial shipment settings gain value System
(S) + 10 CH4 Industrial shipment settings offset value System
(S) + 11 CH4 Industrial shipment settings gain value System