Configuration
18 975-0210-01-01
Generator Start (RC/GS Only)
After setting the clock and selecting a generator, set the
parameters for automatically starting the generator based
upon a battery voltage. Press the up arrow and scroll through
the menus to view the Generator Start menu. Press the
Settings button to select the required setting.
The default Generator Start selection is Manual (Push ON).
This setting disables all automatic start functions. Any other
selection from the Generator Start menu enables the RV
Series Inverter/Charger to automatically start the generator
based upon the battery’s voltage.
The available auto start voltage settings are 11.0, 11.5, 11.8,
12.0, and 12.2 VDC.
Figure 3-11
Select Genset menu items
Note: You cannot set the Auto Gen parameters until you set the
clock.
Note: When the battery voltage drops to the selected generator
start setting, there is a 15-minute delay before the generator starts.
If the battery voltage rises above the generator start setting during
that 15-minute delay, the countdown resets itself and the
generator does not start.
Figure 3-12
Generator Start menu items
Select Genset:
Onan QuietDiesel
Select Genset:
PowerTech Diesel
Select Genset:
Generac Diesel
Generator Start:
Manual (Push ON)
Generator Start:
Auto at 11.0 VDC
Generator Start:
Auto at 12.2 VDC
Generator Start:
Auto at 11.5 VDC
RC-GS_manual.book Page 18 Friday, May 20, 2005 4:57 PM