Operation
38 975-0210-01-01
Over Temperature
The “Otemp/Less Load” System Status message indicates the
inverter/charger transformer and power components have
exceeded a safe operating temperature. Reduce the load on
the inverter. When the unit cools, it automatically resets and
resumes operation. If this condition occurs often, make sure
the inverter is in a cool location, has adequate ventilation, and
the cooling fan is operational.
Overload
The “Overload” System Status message appears when the load
on the inverter/charger exceeds the maximum power rating of
the unit. Reduce the load and restart the inverter/charger by
pressing the On/Off button on the RC/GS and RC7 twice.
Figure 4-13
Over-temperature Error Message
Note: Press any arrow button to cancel the buzzer.
Figure 4-14
Overload Error Message
Inverter
Charge
Batt. Full
Error
822-4A-001
System Status:
Otemp/Less Load
;
Error LED ON
Buzzer sounds
Error Condition
Remedy
Inverter
Charge
Batt. Full
Error
822-4A-001
System Status:
Overload
;
Error LED ON
Buzzer sounds (press
arrow button to cancel)
Error Condition
RC-GS_manual.book Page 38 Friday, May 20, 2005 4:57 PM