3.11.2 HDD TEMP.
The enduring HDD temperature surveillance guarantees an alarm reaction in case the
threshold value is exceeded.
There may be several reasons for HDD temperature excess:
• Exceedance of the max. tolerable ambient temperature (40°C), e.g. upon
installation in an electrical cabinet with inadequate ventilation
• After-effect upon fan failure
• HDD defect
(1) BUZZER: By selecting “ENABLE”, the buzzer is activated upon HDD
temperature excess.
(2) ALARM OUTPUT: Output relay activation.
1: Output relay switches upon alarm.
NONE: no output relay reaction upon alarm.
(3) ALARM DURATION: PERMANENT This value cannot be changed, alarm is
automatically switched off after problem has
been solved.
(4) NETWORK ALARM: YES: Network alarm activated (for settings refer to
NETWORK menu)
Network alarm reception requires optional
PowerCon software.
NO: No network alarm transmission
(5) EMAIL: YES: Alarm email transmission (for settings refer
to NETWORK menu).
NO: No email alarm transmission.
(6) STOP RECORD YES: Recording process is stopped to avoid further
temperature rise and HDD damage.
NO: Recording process continues.
WARNING SETUP MENU
FAN FAULT BUZZER ENABLE
HDD TEMP. ALARM OUTPUT 1
NO HDD ALARM DURATION PERMANENT
HDD FULL NETWORK ALARM NO
EMAIL NO
STOP RECORD YES