LSI AA1167-E1 TV Mount User Manual


 
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 72-Inch Cabinet Site Preparation and Installation Guide
Power Requirements
Table 3 Power Requirements
Unit/Component Requirements
Domestic International
AC Power 250 VAC, 30 A 230 VAC, 32 A
AC Plug NEMA L6-30P, locking plug IEC 309 locking plug
Receptacle 6-30R, receptacle IEC 309 receptacle
Circuit Breaker 20 A
Voltage Range 180 to 257 VAC
Frequency 49 to 50.5 Hz or 59 to 60.6 Hz
Current
(specified frequency)
220 VAC, 50/60 Hz
Configuration A
1
Configuration B
1
Configuration C
1
Operational Current
LP Drives
2
7.35 A 14.70 A 13.16 A
HH Drives
2
7.70 A 15.40 A 13.72 A
Surge Current
LP Drives 10.95 A 21.90 A 22.20 A
HH Drives 11.45 A 22.90 A 23.00 A
1
Power specifications for three configurations containing Low-Profile (LP) and Half-Height (HH) drives, including:
Configuration A contains 1 command module and 5 drive modules
Configuration B contains 2 command modules and 10 drive modules
Configuration C contains 3 command modules and 8 drive modules
2
LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.