16.5 Monitor/Test
Example when data register (D) 32-bit is monitored
Press the [+] button to increase the device number by "2". Press the [-] button to decrease the device number
by "1".
Press and hold the [+] or [-] button for 1 second or more to increase or decrease the value at high speed.
In the case of the list shown below, the screen display is as follows.
3. Test mode operation
1) Press the [OK] button in the monitor mode to change the current value.
The current value blinks while it is being changed.
2) Use the [+] / [-] buttons to change the value as desired.
Press and hold the [+] or [-] button for 1 second or more to increase or
decrease the value at high speed.
3) Press the [OK] button to determine the input. At this time, the input
data is written to the PLC.
Device Current value
D0 (D1) 1000000
D2 (D3) 1500000
D4 (D5) 2000000
[+][+]
[-]
[+]
[-]
[-]
[-]
Changing the current value