Mitsubishi Electronics FX3S-MR/ES Home Theater Server User Manual


 
35
FX3S Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Installation
8
Preparation and
Power Supply
Wiring
9
Input Wiring
10
High-Speed
Counters
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.5 Performance Specifications
*1. The current time of the clock is backed up by the capacitor built-in the PLC. Supply the power to the
PLC for 30 minutes or more to completely charge this large-capacity capacitor.
(The capacitor works for 10 days (atmosphere: 25 °C)
High-speed counter
1-phase 1-count input in both
directions (32 bits up/down)
(EEPROM keep)
C235 to C245
Counting from -2,147,483,648 to +2,147,483,647
1-phase 2-count input in both
directions (32 bits up/down)
(EEPROM keep)
C246 to C250
2-phase 2-count input in both
directions (32 bits up/down)
(EEPROM keep)
C251 to C255
Data register
(32 bits when
paired)
For general (16 bits) D0 to D127 128 points
For EEPROM keep (16 bits) D128 to D255 128 points
For general (16 bits) D256 to D2999 2744 points
File register
(EEPROM keep)
D1000 to D2999 Max. 2000 points
Can be set as file registers in units of
500 points from D1000 in the program
area (EEPROM) using parameters.
For special (16 bits) D8000 to D8511 512 points
For index (16 bits)
V0 to V7
Z0 to Z7
16 points
Pointer
For branching of JUMP and
CALL
P0 to P255 256 points
For CJ instructions and CALL
instructions
Input interruption I0 to I5 6 points
Timer interruption I6 to I8 3 points
Nesting For master control N0 to N7 8 points For MC instructions
Constant
Decimal number (K)
16 bits -32,768 to +32,767
32 bits -2,147,483,648 to +2,147,483,647
Hexadecimal number (H)
16 bits 0 to FFFF
32 bits 0 to FFFFFFFF
Real number (E) 32 bits
-1.0 x 2
128
to -1.0 x 2
-126
, 0 , 1.0 x 2
-126
to 1.0 x 2
128
Decimal-point and exponential notations are possible.
Item Performance