8. BASIC PROGRAMMING
8.3 °C/°F Computation Selection
This programming is to select a “°C” or “°F” computation for a temperature range (thermocouple or resistance
thermometer). The default setting is “°C”. Press and simultaneously 3 seconds or more in the
operation screen to display the “°C/°F computation” selection screen. Select “°F” if necessary.
1 Programming Mode



2 Programming Flow Chart
<Example> From “°C” computation to “°F” computation
Operation screen
[Check]


[To be ready for programming]


[Selecting “°F”]
or


Stored
°C= (°F - 32), °F= x °C + 32
The selected computation unit can be
checked. The unit in the left flow is
°C”.
Cursor and programming lamp light.
Each time or is
pressed,

or

is
displayed alternately.
The selected computation unit is
stored into memory.
Memory colon blinks and the
programming change mark is
printed.
1) In case of temperature unit “K”
The temperature unit for the range No.47 (AuFe-CR) and 80 (Pt-Co) is “K”. It does not affect this
programming.
2) Influence onto other programmed parameters
The programmed parameters for “Range/Printing range”, “Scale” and “Alarm setpoint” are not changed
automatically. If the programmed parameters cannot be used for the selected computation unit, reprogram
them again. Even if “°C” or “°F” is programmed at the “Engineering unit programming”, it does not change
the computation.
Cursor
3 sec. or
more
Computation unit
5
9
9
5
°C” °F” conversion formula
Relation with other programming items
Remarks
Memory
colon
Character display
Programming lamp
DISP
SHIFT
SET
END
%
/
ENTRY
/
%
SHIFT