Calculate the Summary of the whole system’s power consumption.
For example, there are following items in your system.
ADAM-5550KW * 3 & ADAM-5024 * 2 & ADAM-5017 * 4 &
ADAM-5068 * 2 & ADAM-5056D * 2
The power consumption is:
17 W * 3 + 2.9 W * 2 + 1.25 * 4 + 1.8 W * 2 + 0.84 W * 2 = 67.08 W
Table 2.3: Power Consumption of ADAM-5000 series (IO Modules)
ADAM-5013 3-Channel RTD Input Module 1.1 W
ADAM-5017 8-Ch Analog Input Module (mV, mA or High Voltage) 1.25 W
ADAM-5017UH
8-CH Ultra High speed Analog Input Module (mV, mA
or High Voltage)
2.2 W
ADAM-5018
7-Channel Thermocouple Input Module (mV, V, mA,
Thermocopule)
0.63 W
ADAM-5024 4-Channel Analog Output Module (V, mA) 2.9 W
ADAM-5050 16-Channel Universal DIO 1.2 W
ADAM-5051 16-Channel Digital Input Module 0.53 W
ADAM-5051D 16-Channel Digital Input w/LED Module 0.84 W
ADAM-5056S 16-Channel Isolated Digital Input w/LED Module 0.8 W
ADAM-5056SO 16-Channel Digital Input w/LED Module 0.84 W
ADAM-5052 8-Channel Isolated DI 0.27 W
ADAM-5055S 16-Channel Isolated DIO w/LED Module 0.68 W
ADAM-5056 16-Channel Digital Output Module 0.53 W
ADAM-5056D 16-Channel Digital Output w/LED Module 0.84 W
ADAM-5056S 16-Channel Isolated Digital Output w/LED Module 0.6 W
ADAM-5060
6-Ch Relay Output Module ( 2 of Form A, 4 of Form
C)
1.8 W
ADAM-5068 8-Channel Relay Output Module ( 8 Form A) 1.8 W
ADAM-5069 8-Channel Power Relay Output Module ( 8 Form A) 2.2 W
ADAM-5202 2-Ring AMONet Motion Control Module 2.5 W