SPYDER® BACNET® PROGRAMMABLE CONTROLLERS
63-2689—05 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
SPECIFICATIONS
General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on models PVL0000AS, PVL4022AS and
PVL6436AS).
Controller Only Load: 5 VA maximum; models PUB1012S,
PUB4024S, PUB6438S, PVB4024NS and PVB6438NS.
Controller and Actuator Load: 9 VA maximum; models
PVL0000AS, PVL4022AS and PVL6436AS.
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum.
VAV Operating & Storage Temperature Ambient Rating
(models PVB0000AS, PVB4022AS, PVB4024NS,
PVB6436AS and PVB6438NS):
Minimum 32 ºF (0 ºC); Maximum 122 ºF (50 ºC)
Unitary Operating & Storage Temperature Ambient Rating
(models PUB1012S, PUB4024S and PUB6438S):
Minimum -40 ºF (-40 ºC); Maximum 150 ºF (65.5 ºC)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
Velocity Pressure Sensor (models
PVB0000AS, PVB4022AS, PVB4024NS,
PVB6436AS and PVB6438NS)
Operating Range: 0 to 1.5 in. H
2
O (0 to 374 Pa)
Series 60 Floating Actuator (models
PVB0000AS, PVB4022AS and PVB6436AS)
Rotation Stroke: 95° ± 3° for CW or CCW opening dampers
Torque Rating: 44 lb-in. (5 Nm)
Run Time for 90° rotation: 90 seconds at 60 Hz
Operating Temperature: -4 ºF to 140 ºF (-20 to 60 ºC)
Real Time Clock
Operating Range: 24 hour, 365 day, multi-year calendar
including day of week and configuration for automatic day-
light savings time adjustment to occur at 2:00 a.m. local
time on configured start and stop dates
Power Failure Backup:
24 hours at 32°F to 100°F (0°C to
38°C), 22 hours at 100°F to 122°F (38°C to 50°C)
Accuracy: ±1 minute per month at 77
°
F (25
°
C)
Digital Input (DI) Circuits
Voltage Rating: 0 to 30 Vdc open circuit
Input Type: Dry contact to detect open and closed circuit
Operating Range: Open circuit = False; Closed circuit = True
Resistance: Open circuit > 3,000 Ohms; Closed circuit < 500
Ohms
Digital Triac Output (DO) Circuits
Voltage Rating: 20 to 30 Vac @ 50/60Hz
Current Rating: 25 mA to 500 mA continuous, and
800 mA (AC rms) for 60 milliseconds
Analog Output (AO) Circuits
Analog outputs can be individually configured for current or
voltage.
ANALOG CURRENT OUTPUTS:
Current Output Range: 4.0 to 20.0 mA
Output Load Resistance: 550 Ohms maximum
ANALOG VOLTAGE OUTPUTS:
Voltage Output Range: 0.0 to 10.0 Vdc
Maximum Output Current: 10.0 mA
Analog outputs may be configured as digital outputs and
operate as follows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc, (22 mA)
Universal Input (UI) Circuits
See Table 2 for the UI circuit specifications.
Table 2. Universal input circuit specifications.
Input
Type
Sensor
Type
Operating
Range
Room/Zone
Discharge Air
Outdoor Air
Temperature
20K Ohm
NTC
-40 to 199
°
F
(-40 to 93
°
C)
Outdoor Air
Temperature
C7031G
a
-40 to 120
°
F
(-40 to 49
°
C)
C7041F
a
-40 to 250
°
F
(-40 to 121
°
C)
PT1000
(IEC751 3850)
-40 to 199
°
F
(-40 to 93
°
C)