T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09 18
Fig. 34. Setup - Sensors - Sensor A - Exit.
1.2.2.5. Exit Sensor A Setup
Press the t button to exit Sensor A selections and return
to the Sensors menu.
or
Use the p and q buttons to highlight EXIT and press the u
button.
Continue with “1.2.3. SENSOR B (Temperature only)”
Fig. 35. Setup - Sensors - Sensor B Menu.
1.2.3. SENSOR B (Temperature only)
For two-sensor reset control, Sensor B must always be
the controlling temperature. For example, in a reset
control based on outside temperature, Sensor B must be
the outside sensor.
NOTE: Sensor B is available only for reset on the
T775U2006, but can be controlled just like
Sensor A on the T775U2016.
1. From the Sensors menu, use the q button to high-
light SENSOR B.
2. Press the u button to display the Sensor B menu.
3. Repeat the selections described in “1.2.2. SENSOR
A” through “1.2.2.4. LABEL (Sensor A or B input)”
beginning on page 15, but perform only those steps
applicable to Sensor B.
4. Press the t button to exit SENSOR B and return to
the Sensors menu.
or
Use the p and q buttons to highlight EXIT and press
the u button.
5. Press the t button to exit the Sensors menu and
return to the Setup menu.
Continue with “1.3. Setting up the Outputs”.
Fig. 36. Setup - Outputs Menu.
1.3. Setting up the Outputs
1. From the Setup menu, use the pand q buttons to
highlight OUTPUTS.
2. Press the u button to display the Outputs menu.
NOTE: The menus (e.g. the Outputs menu shown
here) can display only those relays that are
defined in Setup (see page 22). For example,
if you configure only two relays, then only
two relays display on the appropriate menus.
The following procedures set up each modulating output
and relay output.
SETUP
SENSORS
SENSOR A
UNITS
CALIBRATE
LABEL
EXIT
M24596
SETUP
SENSORS
SETUP
SENSORS
# SENSORS
SENSOR A
SENSOR B
EXIT
M24597
SETUP
OUTPUTS
MOD 1
SETUP
OUTPUTS
MOD 1
TYPE
MIN OUT %
INTEGRAL
DERIVATIV
SCHEDULE
RESET
HIDE
EXIT
M24599
A