Honeywell T755U Home Theater Server User Manual


 
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
33 62-0255—09
Fig. 75. Program - Setpoint Offset (MOD 2 only).
Fig. 76. Reset Curve with Offset for MOD 2.
3.3. Second Modulating Output and
Relays
For the second Modulating Output and the two Relays (if
they are configured for Reset), the Offset parameter
displays on the Program menu as shown in Fig. 75.
3.3.1. SETPOINT OFFSET (MOD 2 only)
This value is the number of degrees plus (+) or minus (-)
that you want the temperature to be offset from the
MOD 1 setpoint. See Fig. 76. For example, If you want the
MOD 2 setpoint to be 10°F less than the MOD 1 setpoint,
enter -10°F.
1. From the menu, use the p and q buttons to highlight
OFFSET.
2. Press the u button to display the value.
3. Use the p and q buttons to increase/decrease the
desired temperature.
OFFSET Default: 0°F
OFFSET Range: -150°F to 150°F (-101°C to
66°C)
4. Press the u button to accept the value and display
the next option.
3.3.2. Second Modulating Output and
Relays Programming
To complete the programming of MOD 2 or a Relay,
perform the procedures in “3.2.5. THROTTLING RANGE
or DIFFERENTIAL” through “3.2.7. SETBACK OFFSET (if
configured)” beginning on page 31.
3.4. Exit Programming with Reset
When you finish programming the Modulating outputs and
the Relays, press the HOME button to leave programming
mode and return to the home screen.
This completes the programming procedure for controllers
that use Reset.
PROGRAM
MOD 2
MENU
PROGRAM
MOD 2
OFFSET
-10
F
o
ENTER
SETPOINT
OFFSET
FOR
MOD 2
M24547
MENU
PROGRAM
MOD 2
OFFSET
THROT RNG
ACTION
SETBACK
EXIT
SENSOR B
SP MAX A1
(BOILER MAX)
SP MIN A2
(BOILER MIN)
200
140
10
MOD 2
SETPOINT
OFFSET
-10°F
190
20
30 40 50 60
70
°F80
150
160
170
210
220
180
°F
RESET B1
(OUTSD MIN)
RESET B2
(OUTSD MAX)
S
E
N
S
O
R
A
M24569
MOD 1
SETPOINT