12.2 External Wiring of Transistor Output (Sink/Source) Type
2. Transistor output (Source)
*1. The output circuit of this PLC does not have a built-in fuse.
Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by
output element fracture due to load short-circuiting.
*2. "•" represents vacant terminals.
WIRING PRECAUTIONS
Do not wire the vacant terminals externally.
Doing so may damage the product.
100 to 240 V AC
PL
Power ON
Emergency
stop
MC
MC
MC MC
Power supply for load
connected to PLC output
For details on emergency
stop operation, refer to
"DESIGN PRECAUTIONS"
at "Safety Precautions" field.
Breaker
Fuse
*1
Main unit
transistor output (source)
Y000
+V0
Y001
Y002
+V2
+V1
*2
Y005
•••
Load
Fuse
*1
Load
DC power supply
+