Mitsubishi Electronics FX3S-MT/ESS Home Theater Server User Manual


 
30
FX3S Series Programmable Controllers
User's Manual - Hardware Edition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.2 Power Supply Specifications
4.1.1 Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltage between each
terminals and the main unit ground terminal.
4.2 Power Supply Specifications
The power supply specifications for the main unit are explained below.
4.2.1 AC power type
*1. This item shows values when all 24 V DC service power supplies are used in the maximum
configuration connectable to the main unit, and includes the input current (5 or 7 mA per point).
4.2.2 DC power type
*2. There power consumption values are maximum values which include consumption of all expansion
equipment and input current (5 or 7 mA per point).
Terminal Dielectric strength
Insulation
resistance
Remark
Terminals of main unit
Between power supply terminal (AC power) and
ground terminal
1.5 kV AC for 1 min
5 M or more by
500 V DC megger
-
Between power supply terminal (DC power) and
ground terminal
500 V AC for 1 min
-
Between input terminal (24 V DC) and ground
terminal
-
Between output terminal (relay) and ground
terminal
1.5 kV AC for 1 min -
Between output terminal (transistor) and ground
terminal
500 V AC for 1 min -
Main unit analog input terminal and ground
terminal
Not allowed Not allowed -
Terminals of expansion boards, special adapters
Between terminal of expansion board (except
FX
3G-4EX-BD and FX3G-2EYT-BD) and ground
terminal
Not allowed Not allowed
Since the expansion board and the main
unit CPU are not insulated, it is not
allowed to perform the dielectric withstand
voltage test and insulation resistance test
between them.
Between FX
3G-4EX-BD input terminal (24 V DC)
and ground terminal
500 V AC for 1 min
5 M or more by
500 V DC megger
-
Between FX3G-2EYT-BD output terminal
(transistor) and ground terminal
-
Between terminal of special adapter and ground
terminal
-
Item
Specification
FX3S-10M/E FX3S-14M/E FX3S-20M/E FX3S-30M/E
Supply voltage 100 to 240 V AC
Allowable supply voltage range 85 to 264 V AC
Rated frequency 50/60 Hz
Allowable instantaneous power
failure time
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
Power fuse 250 V 1 A
Rush current 15 A max. 5 ms or less/100 V AC, 28 A max. 5 ms or less/200 V AC
Power consumption
*1
19 W 19 W 20 W 21 W
24 V DC service power supply 400 mA
Item
Specification
FX3S-10M/D FX3S-14M/D FX3S-20M/D FX3S-30M/D
Supply voltage 24 V DC
Allowable supply voltage range 20.4 to 26.4 V DC
Allowable instantaneous power
failure time
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
Power fuse 250 V 1.6 A
Rush current 20 A max. 1 ms or less/24 V DC
Power consumption
*2
6 W 6.5 W 7 W 8.5 W
24 V DC service power supply -