5 UTILITY PACKAGE (GX Configurator-AD)
5.4 Initial Setting
[Purpose of setting]
The following A/D initial setting parameters are set:
• A/D conversion enable/disable setting
• Sampling process/averaging process setting
• Time/number of times specifying
• Average time/average number of times setting
By performing these initial settings, the sequence program settings are not required.
[Startup procedure]
"Start I/O No. " "Package name" "Module model name" Initial setting
[Setting screen]
[Explanation of items]
(1) Setting contents
Set whether A/D conversion is enabled or disabled and the A/D conversion
method for each channel.
(2) Explanation of command buttons
Make text file
Outputs the screen display in text file format.
End setup
Confirms the setting data and ends the operation.
Cancel
Cancels the setting data and ends the operation.
POINT
Initial settings are stored in the intelligent function module parameters. After the
initial settings are written to the CPU module, they are validated by operating the
RUN-STOP switch as follows, STOP
RUN STOP RUN, turning the power
OFF and then ON, or resetting the CPU module.
When using a sequencer program to write the initial settings, when the CPU is
switched from STOP to RUN the initial settings will be written, So ensures that
programming is carried out to re-execute the initial settings.