Mitsubishi Electronics Q64AD TV Converter Box User Manual


 
5 - 22 5 - 22
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-AD)
(2) User range saving
(a) Change the Setting value field of pass data read request to "Request", and
click the Execute test
button.
When read is completed, the values are displayed in the Current value fields
of CH
industrial shipment settings offset/gain values/CH user range
settings offset/gain values.
(b) Compare the values with those in the range reference table, and record
them if they are correct.
Refer to Section 7.4 for the range reference table.
(3) User range restoration
(a) Set the recorded values in the Setting value fields of CH industrial
shipment settings offset/gain values/user range settings offset/gain values.
(b) Select all the Setting value fields of CH
industrial shipment settings
offset/gain values/user range settings offset/gain values, and click the
Execute test
button.
When write is completed, the set values are displayed in the Current value
fields of CH
industrial shipment settings offset/gain values/ CH user
range settings offset/gain values.
(c) Change the Setting value field of pass data write request to "Request", and
click the Execute test
button.
Make sure that the indication in the Current value field of pass data write
request changes from "Request" to "OFF" on completion of write.