Mitsumi electronic 13JX10 Universal Remote User Manual


 
14
Remote net Ver.1 mode A mode used to configure a system only with a master station and Ver.1-compatible slave station.
Data can be communicated with all stations (remote I/O station, remote device station, local station,
intelligent device station, and standby master station) in a CC-Link system.
Remote net Ver.2 mode A mode used to configure a system containing master stations and Ver.2-compatible slave stations or to
add Ver.2-compatible slave stations in future.
Data can be communicated with all stations (remote I/O station, remote device station, local station,
intelligent device station, and standby master station) in a CC-Link system.
Compared to the remote net Ver.1 mode, the number of cyclic points per station is increased from 128
to 896 for RX/RY, and from 16 to 128 for RWr/RWw.
Remote register (RWr) Word data input from a slave station to the master station (For some areas in a local station, data are
output in the opposite direction.)
Remote register (RWw) Word data output from the master station to a slave station (For some areas in a local station, data are
output in the opposite direction.)
Link scan (link scan time) Time required for all stations in a system to transmit data. The link scan time depends on data volume
and the number of transient transmission requests.
Link device A device (RX, RY, RWr, RWw, SB, or SW) in a CC-Link module
Link special relay (SB) Bit data that indicates the operating status and data link status of modules on the master and local
stations
Link special register (SW) Word data that indicates the operating status and data link status of modules on the master and local
stations
Local station A station that performs cyclic transmission and transient transmission with the master station and other
local stations.
Term Description