7 COMMUNICATION EXAMPLES
7.1 Example of Communications Between a Master Station and a Remote Device Station
11. In "Remote Device Initial Setting Procedure Registration" window, right-click the icon and click "Hexadecimal" of the
"Input Format". Set the contents of the initial settings in the following item.
• Initial setting for an AJ65VBTCU-68ADVN (station No.1)
Setting the initial setting executes the following processing from the first condition.
Condition Description
1st The CH.1 and CH.2 are set to the A/D conversion enable.
2nd An input range is set.
• CH.1: 0 to 5V
• CH.2: User range setting 1 (-10 to 10V)
3rd Whether a averaging processing or averaging process is executed is set.
• CH.1: Sampling processing
• CH.2: Averaging processing (count average)
4th The average count of the CH.2 is set to 16.
5th Initial data processing completion flag is turned on.
6th Initial data setting request flag is turned on.
7th Initial data processing completion flag is turned off.
8th Initial data setting request flag is turned off.