7 COMMUNICATION EXAMPLES
7.1 Example of Communications Between a Master Station and a Remote Device Station
The assignment by each signal of the AJ65VBTCU-68ADVN and AJ65VBTCU-68DAVN are shown below.
CPU module Remote station
Device Module name RWw Signal name
W100 AJ65VBTCU-68ADVN RWw0 A/D conversion enable/prohibit specification
W101 RWw1 CH.1 to 4 input range setting
W102 RWw2 CH.5 to 8 input range setting
W103 RWw3 Average processing specification
W104 RWw4 CH.1 average time, number of times setting
W105 RWw5 CH.2 average time, number of times setting
W106 RWw6 CH.3 average time, number of times setting
W107 RWw7 CH.4 average time, number of times setting
W108 RWw8 CH.5 average time, number of times setting
W109 RWw9 CH.6 average time, number of times setting
W10A RWwA CH.7 average time, number of times setting
W10B RWwB CH.8 average time, number of times setting
W10C AJ65VBTCU-68DAVN RWw0 CH.1 digital value setting
W10D RWw1 CH.2 digital value setting
W10E RWw2 CH.3 digital value setting
W10F RWw3 CH.4 digital value setting
W110 RWw4 CH.5 digital value setting
W111 RWw5 CH.6 digital value setting
W112 RWw6 CH.7 digital value setting
W113 RWw7 CH.8 digital value setting
W114 RWw8 Analog output enable/disable setting
W115 RWw9 CH.1 to 4 output range setting
W116 RWwA CH.5 to 8 output range setting
W117 RWwB HOLD/CLEAR setting