Cooper B-Line, Inc Cable Tray Manual
UL Listed Conduit To
Cable Tray Clamp
See NEC
®
Table 344.30(B)(2) To Obtain The
Support Requirements For Other Conduit Sizes.
Conduit Terminated On And Supported By The Cable Tray Side Rail.
Installation For Qualifying Industrial Facilities As Per 392.6(J).
16 Feet
2 Inch Rigid Metal Conduit
Position Of The First
Conduit Support
From The Cable Tray
(Conduit Must Be
Securely Fastened To
The Support)
Conduit Bushing
Cable Tray
Side Rail
Cable Tray
UL Listed Conduit To
Cable Tray Clamp
See Section 344.30
Conduit Terminated On The Cable Tray Side Rail.
Installation For Commercial And Non-Qualifying Industrial Facilities As Per 392.6(J).
3 Feet or 5 Feet
Any Size Of Rigid Metal Conduit
Position Of The First
Conduit Support
From The Cable Tray
(Conduit Must Be
Securely Fastened To
The Support)
Conduit Bushing
Cable Tray
Side Rail
Cable Tray
392.7. Grounding. (A) Metallic Cable
Trays.
All metallic cable trays shall be grounded as
required in Article 250 regardless of whether or not
the cable tray is being used as an equipment
grounding conductor (EGC).
The EGC is the most important conductor in an
electrical system as its function is electrical safety.
There are three wiring options for providing an
EGC in a cable tray wiring system: (1) An EGC
conductor in or on the cable tray. (2) Each
multiconductor cable with its individual EGC
conductor. (3) The cable tray itself is used as the
EGC in qualifying facilities.