TOSHIBA- 23
TX Series 48 - 1250A
5.1 Setpoints Page List
The following charts list each Setpoint Page and the programmable functions within
that page. The applicable section of the manual is also referenced.
5.1.1 Basic Configuration (Setpoint Page 1)
5.1.2 Starter Configuration (Setpoint Page 2)
Chapter 5 - Setpoint Programming
The TX Series has twelve programmable setpoint pages which define the motor
data, ramp curves, protection, I/O configuration and communications. In Section 5.1,
the setpoint pages are outlined in chart form. In Section 5.2 the setpoint pages are
illustrated and defined for easy navigation and programming. Note: Setpoints can
only be changed when the starter is in the Ready Mode. Also the soft start will not
start when it is in programming mode.
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Motor Full Load Amps (FLA) Model dependent
50 - 100% of Unit Max Current Rating (Model
and Service Factor dependent)
SP1.1
Service Factor 1.15 1.00 – 1.3 SP1.2
Overload Class 10 O/L Class 5-30 SP1.3
NEMA Design B A-F SP1.4
Insulation Class B A, B, C, E, F, H, K, N, S SP1.5
Line Voltage 480 208 to 600V SP1.6
Line Frequency 60 50 or 60 HZ SP1.7
Page 1
Basic Configuration
Level 1
No Passowrd Required
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Start Control Mode Start Ramp 1
Jog, Start Ramp 1, Start Ramp 2, Custom
Accel Curve, Start Disabled, Dual Ramp
SP2.1
Jog Voltage Off 5-75%, Off
SP2.2
Start Ramp #1 Type Voltage Current, Voltage, Off
Initial Voltage #1 20% 0-100%
Ramp Time #1 10 sec 0-120 sec
Current Limit #1 350% FLA 200-600 %
Initial Current #1 200% FLA 0-300%
Ramp Time #1 10 sec 0-120 sec
Maximum Current #1 350% FLA 200-600 %
Start Ramp #2 Type Off Current, Voltage, Off
Initial Voltage #2 60% 0-100 %
Ramp Time #2 10 sec 0-120 sec
Current Limit #2 350 % FLA 200-600 %
Initial Current #2 200% FLA 0-600 %
Ramp Time #2 10 sec 0-120 sec
Maximum Current #2 350% FLA 200-600 %
Kick Start Type Off Voltage or Off
Kick Start Voltage 65% 10-100 %
Kick Start Time 0.50 sec 0.10-2.00
Deceleration Disabled Enabled or Disabled
Start Deceleration Voltage 60% 0-100 %
Stop Deceleration Voltage 30% 0-59 %
Deceleration Time 5 sec 1-60 sec
Timed Output Time Off 1-1000 sec, Off
SP2.7
Run Delay Time 1 Sec 1-30 sec, Off
SP2.8
At Speed Delay Time 1 Sec 1-30 sec, Off
SP2.9
Bypass Pull-in Current 100% FLA 90 - 300%
SP2.10
SP2.3
SP2.4
SP2.5
SP2.6
Page 2
Starter Configuration
Level 1
No Passowrd Required