TOSHIBA - 30
TX Series 48 - 1250A
5.1.9 RTD Option Configuration Page 9 Cont’d
5.1.10 Security Set Password Page 10
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
RTD #10 Type Off Same as Stator Phase A1
RTD #10 Description User defined User defined, Up to 15 Characters
RTD #10 Alarm Level Off 0-240C (32-464F), Off
RTD #10 Trip Level Off 0-240C (32-464F), Off
RTD #11 Type Off Same as Stator Phase A1
RTD #11 Description User defined User defined, Up to 15 Characters
RTD #11 Alarm Level Off 0-240C (32-464F), Off
RTD #11 Trip Level Off 0-240C (32-464F), Off
RTD #12 Type Off Same as Stator Phase A1
RTD #12 Description User defined User defined, Up to 15 Characters
RTD #12 Alarm Level Off 0-240C (32-464F), Off
RTD #12 Trip Level Off 0-240C (32-464F), Off
Page 9
RTD Configuration
Level 3
Password Protection
SP9.4
5.1.11 Communications Page 11
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Set Level 2 Password 100 000 – 999 Three Digits SP10.1
Set Level 3 Password 1000 0000 – 9999 Four Digits SP10.2
Page
10
Level
3
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Set Front Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.1
Set Modbus Baud Rate 9.6 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.2
Modbus Address Number 247 1 – 247 SP11.3
Set Access Code 1 1 – 999 SP11.4
Set Link Baud Rate 38.4 KB/sec 2.4, 4.8, 9.6, 19.2, 38.4 KB/sec SP11.5
Remote Start/Stop Disabled Enabled or Disabled SP11.6
Page 11
Communiications
Level 3
Password Protection