A SERVICE OF

logo

TOSHIBA - 80
TX Series 48 - 1250A
Cooling Consideration for Maintaining Ambient Temperature
RATED CURRENT HEAT GENERATED MINIMUM CFM MINIMUM EXP. S.S.
UNITS = AMPS UNITS = WATTS UNITS = CFM UNITS = SQ.FT.
48 216 38 54
78 351 62 88
120 540 95 135
180 810 143 203
220 990 174 248
288 1296 228 324
414 1863 328 466
476 2138 376 534
550 2475 436 619
718 3231 569 808
1006 4527 797 1132
1150 5175 911 1294
1250 5625 990 1406