TX Series 48 - 1250A
MP.1 Metering Menu & Data (Metering Page 1)
Displays the basic current metering data:
Screen 1: Phase A, B, C and ground fault current.
Screen 2: Displays the average current of the % of
imbalance and the motor’s RPM (available
with tachometer input)
Screen 3: Displays the motor load in percent of motor
FLA.
Screen 4: Displays the line frequency and the present
Phase Order.
Screen 5: Displays the percent of the remaining thermal
register. In order for the motor to successfully
start, the percentage must begreater than the
thermal capacity required for a successful
start.
Screen 6: Displays the thermal capacity required to
successfully start the motor.
Screen 7: Displays the average time required to start.
Screen 8: Displays the average current during start.
Screen 9: Displays the measured I
2
T required to start
the motor.
Screen 10: Displays the amount of time required to start
the motor during the last successful start.
MENU
METERING PAGE 1
CURRENT METERED DATA IC: ###### G/F: #####
I (AVG): ####
I/B: ## % RPM: ####
MOTOR LOAD % OF FLA
FLA: ### %
LINE FREQUENCY:: ##.##
PHASE ORDER: ###
THERMAL REGISTER
REMAINING: ### %
THERMAL CAPACITY
TO START: ### %
AVERAGE START TIME
TIME: ##.# SECS
AVG START CURENT
: ###### AMPS
I*I*T TO START
I*I*T: #######
LAST START
TIME: ##.# SEC
IA: ###### IB: ######
Screen 1
Screen 2
Screen 3
Screen 4
Screen 5
Screen 6
Screen 7
Screen 8
Screen 9
Screen 10