TOSHIBA- 53
TX Series 48 - 1250A
MENU
PAGE 11
COMMUNICATIONS
SET FRONT BAUD
RATE: 9.6 KB/SEC
(Hit DOWN ARROW ten times)
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
SET MODBUS BAUD
RATE: 9.6 KB/SEC
MODBUS ADDRESS
NUMBER: 247
SET ACCESS CODE
CODE: 1
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
Range: 1 - 247
Increments of 1
Range: 1 - 999
Increments of 1
SET LINK BAUD
RATE: 38.4 KB/SEC
Range: 2.4, 4.8, 9.6, 19.2
38.4 KB/SEC
REMOTE START/STOP:
DISABLED
Option: Enabled or Disabled
SP.11 Communications (Setpoint Page 11)
(Security Level: 3)
SP11.1 Set Front Baud Rate: Configures the RS232
communications baud rate.
SP11.2 Set Modbus Baud Rate: Configures the modbus
communications baud rate.
SP11.3 Modbus Address Number: Assigns a Modbus
address to the TX relay.
SP11.4 Set Access Code: Assigns an access code to
the Modbus addressing.
SP11.5 Set Link Baud Rate: Configures the RS422
communications baud rate between the keypad
operator and the CPU board. (For applications
with remote keypad only.)