Sentry Industries PT22 Universal Remote User Manual


 
Displaying outlet status
The Status command displays the on/off status of one or more outlets. The command displays the status of
only those outlets for which the current username has power control access.
This display includes the outlet absolute and descriptive names, the Outlet State reported to the Sentry
by the outlet and the current Control State being applied by the Sentry. If you do not specify any
parameter with this command, the status of all accessible outlets is displayed.
NOTE: If the user has access to more than 16 total outlets, the Status command will display the first 16 outlets with a
prompt to view the remaining outlets.
For more information on outlet and control state values, see Outlet Control on page 12.
To display on/off status of one or more outlets:
At the Sentry: prompt, type status, followed by an outlet name, and press Enter, or
Type status, followed by a group name, and press Enter, or
Type status and press Enter.
Examples
The following command displays the on/off status of the outlet named FileServer_1:
Sentry: status FileServer_1<Enter>
Outlet Outlet Outlet Control
ID Name State State
.A3 FileServer_1 On On
The following command displays the on/off status of all accessible outlets:
Sentry: status<Enter>
Outlet Outlet Outlet Control
ID Name State State
.A1 DataServer_1 On On
.B1 WebServer_1 On On
.A3 FileServer_1 On On
.A4 On On
The following command displays the on/off status for outlets in the group ServerGroup_1:
Sentry: status ServerGroup_1<Enter>
Group: ServerGroup_1
Outlet Outlet Outlet Control
ID Name State State
.A1 DataServer_1 On On
.B1 WebServer_1 On On
.A3 FileServer_1 On On
Sentry PT22 Operations 25
Installation and Operations Manual