Sentry Industries PT22 Universal Remote User Manual


 
Displaying outlet information
The Show Outlets command displays information about all outlets. This information includes:
Sequencing and reboot timer values
Descriptive outlet name, if applicable
Outlet wakeup state setting
To display outlet information:
At the Sentry: prompt, type show outlets and press Enter.
Example
The following command displays all outlet information:
Sentry: show outlets<Enter>
Outlet Outlet Wakeup Post-On
ID Name State Delay (seconds)
.A1 DataServer_1 Off 90
.B1 WebServer_1 On 0
.C1 FileServer_1 On 0
.D1 On 0
Outlet Options:
Sequence Interval: 2 seconds
Reboot Delay: 15 seconds
Group Administration
Creating a group name
The Create Group command creates a new group name.
To create a group name:
At the Sentry: prompt, type create group, optionally followed by a descriptive name of up to 24
alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not allowed. Group
names are not case sensitive). Press Enter.
Example
The following command creates group name ServerGroup_1:
Sentry: create group ServerGroup_1<Enter>
Removing a group name
The Remove Group command removes a group name.
To remove a group name:
At the Sentry: prompt, type remove group, optionally followed by a username. Press Enter.
Example
The following command removes group name ServerGroup_1:
Sentry: remove group ServerGroup_1<Enter>
Adding an outlet to a group
The Add OutletToGroup command adds an outlet to a group. To add more than one outlet, but not all
outlets, you must use multiple Add OutletToGroup commands.
To add an outlet to a group:
At the Sentry: prompt, type add outlettogroup, optionally followed by an outlet name and group name.
Press Enter, or
Type add OutletToGroup, followed by all and the group name. Press Enter.
Examples
The following commands uses absolute outlet names to add outlets A1 and B1 to group name
ServerGroup_1:
Sentry:add OutletToGroup .a1 ServerGroup_1<Enter>
Sentry:add OutletToGroup .b1 ServerGroup_1<Enter>
Sentry PT22 Operations 33
Installation and Operations Manual