Sentry Industries PT22 Universal Remote User Manual


 
The following commands usese the outlets’ descriptive names to add outlets DataServer_1 and
WebServer_1 to group name ServerGroup_1:
Sentry:add OutletToGroup DataServer_1 ServerGroup_1<Enter>
Sentry:add OutletToGroup WebServer_1 ServerGroup_1<Enter>
The following command add all outlets to group name ServerGroup_1:
Sentry: add OutletToGroup<Enter>
Outletname: all<Enter>
Groupname: ServerGroup_1<Enter>
Deleting an outlet from a group
The Delete OutletFromGroup command deletes an outlet from a group. To delete more than one outlet,
but not all outlets, you must use multiple Delete OutletToGroup commands.
To delete an outlet from a group:
At the Sentry: prompt, type delete outletfromgroup, optionally followed by an outlet name and a
group name. Press Enter, or
Type delete outletfromgroup, followed by all then the group name. Press Enter.
Environmental Monitor Administration
Creating a descriptive Environmental Monitor name
The Set Envmon Name command assigns a descriptive name to the integrated Environmental Monitor.
This descriptive name is displayed when the Evnmon command is issued.
To create an Environmental Monitor name:
At the Sentry: prompt, type set envmon name, followed by the absolute Environmental Monitor name,
then the descriptive name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126
decimal – spaces are not allowed). Press Enter.
Example
The following command adds the descriptive name Florida_HQ_1to the Environmental Monitor:
Sentry: set envmon name .a Florida_HQ_1<Enter>
Creating a descriptive temperature/humidity sensor name
The Set Envmon THS Name command assigns a descriptive name to a temperature/humidity sensor.
This descriptive name is displayed when the Evnmon command is issued.
To create an temperature/humidity sensor name:
At the Sentry: prompt, type set envmon ths name, followed by the absolute name of the
temperature/humidity sensor, then the descriptive name of up to 24 alphanumeric and other typeable
characters (ASCII 33 to 126 decimal – spaces are not allowed). Press Enter.
Example
The following command adds the descriptive name T/H2_Florida_HQ_1 to the second
temperature/humidity sensor:
Sentry: set envmon ths name .a2 T/H2_Florida_HQ_1<Enter>
Serial Port Administration
Creating a descriptive serial port name
The Set Port Name command assigns a descriptive name to a serial port. You may use this name in
commands that require a port name as an alternative to using the port’s absolute name.
To create an port name:
At the Sentry: prompt, type set port name, followed by the absolute outlet name and a descriptive
name of up to 24 alphanumeric and other typeable characters (ASCII 33 to 126 decimal - spaces are not
allowed). Port names are not case sensitive. Press Enter.
Example
The following command adds the descriptive name Rack1 to Console port:
Sentry: set port name console Rack1<Enter>
34 Operations Sentry PT22
Installation and Operations Manual