Load Trap
The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load
traps include the reported input load, load status, Location of the Sentry, and identifier and name of the
affected infeed.
Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Load returns to a non-error status.
Load traps
Status Error Description
Normal Infeed is on and within preset thresholds
NotOn Infeed is off
Reading Non-error state – Load status currently being read
LoadHigh x Infeed current load exceeds preset threshold
OverLoad x Infeed current load exceeds the measurable range for the infeed
ReadError x Unable to read Load status
NoComm x Communication to the infeed has been lost
Configuring Traps
SNMP Trap Command Summary
Command Description
Set Trap Tower Status Enables or disables the Tower Status trap
Set Trap Infeed Status Enables or disables the Infeed Status trap off
Set Trap Infeed Load Enables or disables the Infeed Load trap
Set Trap Infeed HighThresh Sets the Infeed Load trap high limit
Set Trap Outlet Change Enables or disables the Outlet Change trap
Set Trap Outlet Status Enables or disables the Outlet Status trap
Show Traps Displays trap configurations
Enabling or Disabling a Status trap
The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed or Outlet.
To Enable or Disable a Status trap:
At the Sentry: prompt, type set trap (tower, infeed or outlet) status, followed by the tower, infeed or
outlet name, and on or off. Press Enter, or\
Type set trap (tower, infeed or outlet) Status all, followed by on or off and press Enter.
Examples
The following command enables the Status trap for the first tower, using the tower’s absolute name:
Sentry: set trap tower status .a on<Enter>
The following command enables the Status trap for the tower named Florida_HQ_1:
Sentry: set trap tower status Florida_HQ_1 on<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Outlet
Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a Tower Status trap is
disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.
Sentry Commander - PT40 Advanced Operations 47