Enabling or Disabling a Load trap
The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.
To Enable or Disable a Load trap:
At the Sentry: prompt, type set trap infeed load, followed by the infeed name, and on or off. Press Enter, or
Type set trap infeed load all, followed by on or off and press Enter.
Examples
The following command enables the Load trap for second infeed on the first tower, using the infeed’s
absolute name:
Sentry: set trap infeed load .AB on<Enter>
The following command disables the Load trap for all infeeds:
Sentry: set trap infeed load all off<Enter>
NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling an Infeed
Load trap automatically enables the Infeed and Tower Status traps for that infeed.
Setting the Infeed Load limit
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Sentry: prompt, type set trap infeed loadhigh, followed by the infeed name, and a value from 0
to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25
amperes, using the infeed’s absolute name:
Sentry: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling a Change trap
The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the Sentry: prompt, type set trap outlet change, followed by the outlet name and on or off. Press Enter, or
Type set trap outlet change all, followed by on or off and press Enter.
Example
The following command enables the Change trap for the third outlet on the first infeed of the second
tower, using the outlet’s absolute name:
Sentry: set trap outlet change .ba3 on<Enter>
48 • Advanced Operations Sentry Commander - PT40
Installation and Operations Manual