Emerson 3098 Universal Remote User Manual


 
Electrical Connections 3098 Technical Manual
3-10
3.5.6 7955 3-wire configuration
3098 7955 Flow Computer
1
+
SIG A
2
-
3
+
SIG B
4
-
+24V DensitySK3/35
Ch.1
SK1/31
SK1/32
SK3/19
SK3/35
Ch.2
SK1/48
SK1/49
SK3/19
Density Sig +
Density Sig -
0V Density
Figure 3-5.24 : 7955 Flow Computer
Gas Specific Gravity 3-Wire System (Safe Area)
3098 7955 Flow Computer
1
+
SIG A
2
-
3
+
SIG B
4
-
Hazardous Area Safe Area
MTL 787 (+ve)
3
4
1
2
+24V DensitySK3/35
Ch.1
SK1/31
SK1/32
SK3/19
SK3/35
Ch.2
SK1/48
SK1/49
SK3/19
Density Sig +
Density Sig -
0V Density
Figure 3-5.25: 7955 Flow Computer
Gas Specific Gravity 3-Wire System with Shunt-Diode Safety Barrier (Hazardous Area)
3098 7955 Flow Computer
1
+
SIG A
2
-
3
+
SIG B
4
-
MTL 5032
4
1
14
13
Hazardous Area Safe Area
5 12
11
2kR
+24V DensitySK3/35
Ch.1
SK1/31
SK1/32
SK3/19
SK3/35
Ch.2
SK1/48
SK1/49
SK3/19
Density Sig +
Density Sig -
0V Density
Note: Switches on MTL5032 should be set to give a threshold voltage of 3 volts
Figure 3-5.26: 7955 Flow Computer
Gas Specific Gravity 3-Wire System with Galvanic Isolator (Hazardous Area)