Phonetics Boat Remote Universal Remote User Manual


 
Boat Remote Users Manual
50
Bilge Pump Inputs (2)
The Bilge Pump Inputs will monitor the number of on/off cycles and
the accumulated run time of your bilge pumps. The alarm param-
eters can be programmed to detect whether the bilge pump runs too
frequently (cycle rate alarm) or for too long a period (maximum run
time alarm). To aid in determining the appropriate alarm parameters
for your boat, set the input mode to status only and monitor the
display for a day or so. It will show bilge pump activity as follows:
Bilge Pump 1 OFF
Cycle: 0 Time:0:00
Max Cycle Rate: 0
Max Runtime: 0:00
1. The real time status, on or off, of the bilge pump.
2. Number of cycles and accumulated run time over a 24 hour
period starting at 12 am. (This resets to 0 at 12 am)
3. Maximum # of cycles over the programmed cycle rate alarm
period.
4. Maximum run time of any one cycle.
To program the bilge pump alarm parameters:
Press
SET.
Press BILGE #1 or BILGE #2.
or
The input mode will be displayed. Press the MODE key on the keypad
until the appropriate mode is shown on the display. The default for
bilge #1 is active. The default for bilge #2 is off. Press ENTER.
Press the
MODE key to toggle through the three input modes.
Press ENTER.