Emerson 5300 TV Converter Box User Manual


 
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-12
6. Connect to the transmitter and perform the necessary configuration.
7. After completing the configuration, disconnect the RS-485 Converter,
connect the Modbus communication wires and cycle power to the
transmitter
8. Verify communication between the transmitter and the RTU is
established (can take up to 60 seconds from startup).
NOTE
Take the following into consideration if there are multiple 5300/5400 Modbus
units on the bus:
By default, the transmitters have HART address 1. It will not be possible to
establish communication on HART address 1 if several transmitters have the
same address. In this case, there are alternative solutions to establish
communication:
1. Select the Scan by Tag option in the Search Device window in RRM and
enter the HART Device Tag of the transmitter. Communication can now
be established with an individual transmitter even if several devices have
the same HART address.
2. Make sure the 5300/5400 transmitter is alone on bus. Disconnect or turn
off power from any other devices.
Connect to the HART
terminals
To configure the 5300/5400 transmitter, connect the communicator or PC to
the HART terminals using a HART modem, see Figure 1-3 on page 1-6. Both
the configuration tool and the RS-485 bus can be connected simultaneously.
Configuration data is sent with HART commands through the HMC to the
5300/5400 transmitter electronics, as illustrated in Figure 1-1 on page 1-3.
Note that the power supply must be connected during configuration, see also
“Electrical Installation” on page 1-4.
NOTE
Measurement data is not updated to the Modbus Master when a configuration
tool is connected.