Rosemount 5300/5400 Series
1-18
Levelmaster Parameter Configuration Example
You want to use address 2 for the 5300/5400 transmitter and the host uses
the following parameters:
Table 1-7. Parameters Used by the
Host (in case of Levelmaster,
example)
To configure the 5300/5400 transmitter to communicate with the Host in this
example, the following text string is written to the Modbus Message area.
HMC M2 A2 B9600 D7 PN S1.
NOTE
Include all the parameters when writing to the message area.
Note that an address must be unique on the bus.
HMC: These three letters are used for safety and will eliminate the risk of
changing the configuration data by mistake.
M2: This means that the Levelmaster protocol is to be used.
A2: A indicates that the following is the new address (address 2). Leading
zeroes are not needed.
B9600: B indicates that the following number is the new baud rate (1200,
2400, 4800, 9600, 19200).
D7: D indicates that the following data bits are to be used (7 = seven,
8 = eight).
PN: P identifies the following letter as parity type (O = odd, E = even, and
N = none).
S1: S indicates that the following figure is the number of stop bits (1 = one,
2 = two).
Note: Start Bits are not configurable and cannot be set.
Parameter Value
Baud Rate 9600
Start Bits One
Data Bits Seven
Parity None
Stop Bits One