Emerson 5300 TV Converter Box User Manual


 
Manual Supplement
00809-0500-4530, Rev AA
October 2010
1-31
Rosemount 5300/5400 Series
Emerson Process Management
FloBoss 107
Figure 1-10. Wiring Diagram for
Connecting 5300/5400 Modbus to
Emerson Process Management
FloBoss 107
Table 1-20. Parameter Values (in
case of Emerson Process
Management FloBoss 107)
The Input Register Base Number needs to be added to the Input Register
address of the 5300/5400 transmitter. In this case, register 1300 needs to
have 1300 entered as the address.
ABB TotalFlow
Figure 1-11. Wiring diagram for
connecting 5300/5400 Modbus to
ABB TotalFlow
Table 1-21. Parameter Values (in
case of ABB TotalFlow)
The Input Register Base Number needs to be added to the Input Register
address of the 5300/5400 transmitter. In this case, register 1302 needs to
have 1303 entered as the address etc.
RS-485
A
B
NC
NC
PWR
GND
MA
MB
POWER +
POWER -
FloBoss 107
5300/5400 Modbus
Power Supply
+ 8 to + 30 Vdc
(max. rating)
GND
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Conversion Code 66
Input Register Base Number 0
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type 16 Bit Modicon
Input Register Base Number 1