Emerson 5300 TV Converter Box User Manual


 
Manual Supplement
00809-0500-4530, Rev AA
October 2010
Rosemount 5300/5400 Series
1-40
SPECIFICATIONS
Table 1-26. Specifications
See the Rosemount 5300 Series Reference Manual (Document No.
00809-0100-4530), and the Rosemount 5400 Series Reference Manual
(Document No. 00809-0100-4026) for further specifications.
Power supply 8-30 Vdc (max. rating)
Power consumption
< 0.5 W (with HART address=1)
< 1.2 W (incl. four HART slaves)
Signal wiring
Two-wire half duplex RS-485 Modbus. Use shielded
twisted pair wiring, preferably with an impedance of 120
(typically 24 AWG), in order to comply with EIA-485
standard and EMC regulations.
Power supply cabling
The power supply cables must be suitable for the supply
voltage and ambient temperature, and approved for use
in hazardous areas, where applicable.
Ground (common mode)
voltage limit
± 7 V
Bus termination Standard RS-485 bus termination per EIA-485